Installing and putting a SINAUT modem into operation
5.7 Analog dial-up modem MD3
Station control system
System Manual, 07/2009, C79000-G8976-C178-07
237
a terminal program before it can be put into operation (for details see section
User-
configurable profiles
).
The procedure is as follows:
Turn of the power supply and set the four switches SW2.1 to SW2.4 to the required position.
When you turn on the power supply, the modem then adopts the selected standard dialing
profile.
The following table lists the properties of the individual dialing profiles and how to set them
using the switches mentioned above.
Table 5- 30 Setting standard dialing profiles
Profile no. Meaning Setting on DIL switch
0 AT mode


2))
21
1 V.25bis
1200 bps duplex, V.22


2))
21
2 V.25bis
2400 bps duplex, V.22bis


2))
21
3 V.25bis
4800 bps duplex, V.32bis


2))
21
4 V.25bis
9600 bps duplex, V.32bis


2))
21
5 V.25bis
19200 bps duplex, V.34bis


2))
21
6 V.25bis
33600 bps duplex, V.34bis


2))
21
7 AT mode
Freely configurable


2))
21