Loading...
Digital outputs min. Standard max. Nominal
Maximum switching frequency
Resistive load - - 100 Hz -
Inductive load - - 2 Hz -
Lamp - - 11 Hz -
1)
U
H_typical
= V
CC
- I
OUT
× R
ON
V
CC
: Current operating voltage
I
OUT
: Output current
Maximum short-circuit current: 4 A (max. 100 μs, V
CC
= 24 V)
R
ON
: Maximum internal resistance = 0.4 Ω
2)
Where demand factor is 100% (all outputs active)
Incorrect connection causes neither high level nor destruction of the outputs.
9.2.4 Parameter assignment
9.2.4.1 Input / output images
Input image
The image comprises 2 slots (n, d ≙ start address):
Slot 1: Digital inputs (DI)
n+0 … n+8 (9 byte)
X222.P3 - .P10 are rapid inputs
Slot 2: Diagnostics: d+0 .. d+1
Table 9-26 Input image of digital inputs for the 1st I/O module (n=0)
Terminal Byte Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
X111
n+0 Pin10
DI 0.7
Pin9
DI 0.6
Pin8
DI 0.5
Pin7
DI 0.4
Pin6
DI 0.3
Pin5
DI 0.2
Pin4
DI 0.1
Pin3
DI 0.0
n+1 Pin18
DI 1.7
Pin17
DI 1.6
Pin16
DI 1.5
Pin15
DI 1.4
Pin14
DI 1.3
Pin13
DI 1.2
Pin12
DI 1.1
Pin11
DI 1.0
n+2 Pin26
DI 2.7
Pin25
DI 2.6
Pin24
DI 2.5
Pin23
DI 2.4
Pin22
DI 2.3
Pin21
DI 2.2
Pin20
DI 2.1
Pin19
DI 2.0
X222
n+3 Pin10
DI 3.7
Pin9
DI 3.6
Pin8
DI 3.5
Pin7
DI 3.4
Pin6
DI 3.3
Pin5
DI 3.2
Pin4
DI 3.1
Pin3
DI 3.0
n+4 Pin18
DI 4.7
Pin17
DI 4.6
Pin16
DI 4.5
Pin15
DI 4.4
Pin14
DI 4.3
Pin13
DI 4.2
Pin12
DI 4.1
Pin11
DI 4.0
n+5 Pin26
DI 5.7
Pin25
DI 5.6
Pin24
DI 5.5
Pin23
DI 5.4
Pin22
DI 5.3
Pin21
DI 5.2
Pin20
DI 5.1
Pin19
DI 5.0
Connectable components
9.2 PP 72/48D PN
NCU 7x0.3B PN
Equipment Manual, 10/2020, 6FC5397-1EP40-6BA1 115