4.4.2 LED displays
Meaning of the RUN/STOP, ERROR and MAINT PLC-LEDs
RUN/STOP LED ERROR LED MAINT LED Meaning
LED o LED o LED o
Supply voltage at the PLC not present or too low.
LED o
LED ashes red
LED o
An error has occurred.
LED lights up green
LED o LED o
The PLC is in the RUN operating state.
LED lights up green LED ashes red
LED o
Diagnostic event pending.
LED lights up green
LED o
LED lights up yellow
A plant maintenance request is pending.
The aected hardware must be validated/replaced
within a short interval.
Active force job
PROFIenergy pause
LED lights up green
LED o
LED ashes yellow
A plant maintenance requirement is pending.
The aected hardware must be validated/replaced
within a foreseeable interval.
Conguration faulty
LED lights up yellow
LED o
LED ashes yellow
Firmware update completed successfully.
LED lights up yellow
LED o LED o
The PLC is in the STOP operating state.
LED lights up yellow LED ashes red LED ashes yellow
The program from the internal PLC memory causes
an error.
PLC defective
LED ashes yellow
LED o LED o
The PLC performs internal activities during STOP,
e.g. ramp-up after STOP.
Loading the user program from the internal PLC
memory.
LED ashes
yellow/green
LED o LED o
Startup (transition from RUN → STOP)
LED ashes
yellow/green
LED ashes red LED ashes yellow
Startup (booting the PLC)
Test the LEDs during startup, insert a module.
LED ash test
Description
4.4Operator control and display elements
NCU 1750
Equipment Manual, 10/2023, A5E45627807B AH 37