2 Functions
234
7UT613/63x Manual
C53000-G1176-C160-2
9034 RTD 3 STAGE 1 -58 .. 482 °F; 212 °F RTD 3: Temperature Stage 1
Pickup
9035 RTD 3 STAGE 2 -50 .. 250 °C; 120 °C RTD 3: Temperature Stage 2
Pickup
9036 RTD 3 STAGE 2 -58 .. 482 °F; 248 °F RTD 3: Temperature Stage 2
Pickup
9041A RTD 4 TYPE Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 4: Type
9042A RTD 4 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 4: Location
9043 RTD 4 STAGE 1 -50 .. 250 °C; 100 °C RTD 4: Temperature Stage 1
Pickup
9044 RTD 4 STAGE 1 -58 .. 482 °F; 212 °F RTD 4: Temperature Stage 1
Pickup
9045 RTD 4 STAGE 2 -50 .. 250 °C; 120 °C RTD 4: Temperature Stage 2
Pickup
9046 RTD 4 STAGE 2 -58 .. 482 °F; 248 °F RTD 4: Temperature Stage 2
Pickup
9051A RTD 5 TYPE Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 5: Type
9052A RTD 5 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 5: Location
9053 RTD 5 STAGE 1 -50 .. 250 °C; 100 °C RTD 5: Temperature Stage 1
Pickup
9054 RTD 5 STAGE 1 -58 .. 482 °F; 212 °F RTD 5: Temperature Stage 1
Pickup
9055 RTD 5 STAGE 2 -50 .. 250 °C; 120 °C RTD 5: Temperature Stage 2
Pickup
9056 RTD 5 STAGE 2 -58 .. 482 °F; 248 °F RTD 5: Temperature Stage 2
Pickup
9061A RTD 6 TYPE Not connected
Pt 100
Ni 120
Ni 100
Not connected RTD 6: Type
9062A RTD 6 LOCATION Oil
Ambient
Winding
Bearing
Other
Other RTD 6: Location