A Appendix
548
7UT613/63x Manual
C53000-G1176-C160-2
A.6 Protocol-dependent Functions
Protocol → IEC
60870-5-103
IEC 61850 Eth-
ernet (EN100)
PROFIBUS
FMS
PROFIBUS
DP
DNP3.0 Modbus
ASCII/RTU
Additional
Service inter-
face
(optional)
Function ↓
Operational
Measured
values
Yes (fixed
values)
Yes Yes Yes Yes Yes Yes
Metered Values Yes Yes Yes Yes Yes Yes Yes
Fault Recording Yes Yes Yes No.
Only via
additional
service inter-
face
No.
Only via
additional
service inter-
face
No.
Only via
additional
service inter-
face
Yes
Remote relay
setting
No.
Only via
additional in-
terface
No.
Only via
additional inter-
face
Yes No.
Only via
additional
service inter-
face
No.
Only via
additional
service inter-
face
No.
Only via
additional
service inter-
face
Yes
User-defined
annunciations
and switching
objects
Yes Yes Yes User-defined
annuncia-
tions in CFC
User-defined
annuncia-
tions in CFC
User-defined
annuncia-
tions in CFC
Yes
Time synchroni-
sation
Via
protocol;
DCF77/IRIG
B;
Interface;
Binary input
Via
protocol (NTP);
DCF77/IRIG B;
Interface;
Binary input
Via
protocol;
DCF77/IRIG
B; inter-
face;binary
input
Via
protocol;
DCF77/IRIG
B;
Interface;
Binary input
Via
protocol;
DCF77/IRIG
B;
Interface;
Binary input
Via
DCF77/IRIG
B;
Interface;
Binary input
-
Annunciations
with time stamp
Yes Yes Yes Yes Yes No Yes
Commissioning tools
Indication mea-
sured value
blocking
YesYes YesNoNoNoYes
Generation of
test annuncia-
tions (DIGSI)
YesYes YesNoNoNoYes
Physical properties
Mode Asynchro-
nous
Synchronous Asynchro-
nous
Asynchro-
nous
Asynchro-
nous
Asynchro-
nous
-
Transmission
mode
Cycli-
cal/event
Cyclical/event Cycli-
cal/event
Cyclical Cycli-
cal/event
Cyclical -
Baud rate 4800 to
38400
up to 100 Mbaud up to 1.5
Mbaud
up to 1.5
Mbaud
2400 to
19200
2400 to
19200
2400 to
38400
Connection to
device
Electrical:
RS232
RS485 opti-
cal: ST con-
nector
Ethernet TP Electrical:
RS485 opti-
cal: ST con-
nector
(single or
double ring)
Electrical:
RS485 opti-
cal: ST con-
nector
(double ring)
Electrical:
RS485 opti-
cal: ST con-
nector
Electrical:
RS485 opti-
cal: ST con-
nector
Electrical:
RS232
RS485 opti-
cal. ST con-
nector
RTD-box 7XV5662-xAD Yes

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT63 series and is the answer not in the manual?

Siemens SIPROTEC 7UT63 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT63 series
CategoryProtection Device
LanguageEnglish

Related product manuals