C53000-G1176-C160-2
4.8 Unbalanced Load Protection 
Characteristics 
Current Stages 
Definite-time stages DT I
2
>>, I
2
>
Inverse time stages
(acc. to IEC or ANSI)
IT I
2P
One of the characteristics shown in figures 4-
14 to 4-17 can be selected
Reset characteristics
with disk emulation
IT For illustrations of possible reset time charac-
teristics see figures 4-14 to 4-17 on the left-
hand side.
Operating Range 0.1 to 4 I/InS
High current stage I
2
>> 0.10 A to 3.00 A
1)
Steps 0.01 A
T
I2
>> 0.00 s to 60.00 s
or ∞ (no trip)
Steps 0.01 s
Definite time current element 
(50Ns-2, 50Ns-1)
I
2
> 0.10 A to 3.00 A
1)
Steps 0.01 A
T
I2
> 0.00 s to 60.00 s
or ∞ (no trip)
Steps 0.01 s
Inverse current element (51Ns-
IEC)
I
2P
0.10 A to 2.00 A
1)
Steps 0.01 A
T
I2P
0.05 s to 3.20 s
or ∞ (no trip)
Steps 0.01 s
Inverse current element (51Ns-
ANSI)
I
2P
0.10 A to 2.00 A
1)
Steps 0.01 A
D
I2P
0.50 s to 15.00 s
or ∞ (no trip)
Steps 0.01 s
Tolerances with inverse time 
2)
currents 3 % of setting value or 1 % nominal current
times 1 % of setting value or 10 ms
Tolerances with definite time (IEC) 
2)
currents Pickup with
1.05 ≤ I
2
/I
2P
 ≤ 1.15
times
5% ± 15 ms
5% ± 45 ms
at f
N
 = 50/60 Hz 
for f
N
 = 16.7 Hz
for 2 ≤ I
2
/I
2P
 ≤ 20
and T
I2P
/s ≥ 1
Tolerances with definite time (ANSI) 
2)
times
5% ± 15 ms
5% ± 45 ms
at f
N
 = 50/60 Hz 
for f
N
 = 16.7 Hz
for 2 ≤ I
2
/I
2P
 ≤ 20
and D
I2P
/s ≥ 1
The set times are pure delay times. 
1)
 Secondary values for I
N
 = 1 A; for I
N
 = 5 A the currents must be multiplied by 5. 
2)
 For one 3-phase measuring location