2.12 Reverse Power Protection
245
7UT613/63x Manual
C53000-G1176-C160-2
2.12 Reverse Power Protection
Reverse power protection is used to protect a turbo-generator unit on failure of energy 
to the prime mover when the synchronous generator runs as a motor and drives the 
turbine taking motoring energy from the network. This condition endangers the turbine 
blades the and must be interrupted within a short time by tripping the network circuit-
breaker. For the generator, there is the additional risk that, in case of a malfunctioning 
residual steam pass (defective stop valves) after the switching off of the circuit break-
ers, the turbine-generator-unit is speeded up, thus reaching an overspeed. For this 
reason, the decoupling should only be performed after the detection of active power 
input into the machine. The reverse power protection can be used as a criteria for the 
decoupling in the system.
The reverse power protection can only be used for a three-phase protective objects. 
This understands that the device is connected to a voltage transformer set and that 
this voltage, together with an assigned corresponding current transformer, allows for 
a logical calculation of the active power. This is therefore only possible for 7UT613 and 
7UT633.
2.12.1 Function Description
Reverse Power De-
termination
The reverse power supervision in 7UT613/63x calculates the active power from the 
symmetrical components of the fundamental waves of the voltages and currents.
There are two measurement methods:
• The "precise" measuring procedure is especially suited for reverse power protec-
tion on generators, as in this case a very low active power is calculated from a very 
high apparent power (for small cos ϕ). The positive sequence systems from voltag-
es and currents are used to obtain a very high accuracy of the last 16 cycles. The 
evaluation of the positive phase-sequence systems makes the reverse power de-
termination independent of current and voltage asymmetries and corresponds to 
actual loading of the drive end. By taking the error angles of the voltage and current 
transformers into account, the active power component is exactly calculated even 
with very high apparent powers and low cos ϕ. The angle correction is performed 
by a correction angle ϕ
corr
 (see Subsection 2.1.4, "General System data"), which is 
appropriately determined by the commissioning of the protective device in the 
system (see Subsection "Installation and Commissioning", "Checking the Voltage 
Connections and Polarity Check").
• The "fast" measurement also uses the positive-sequence components of currents 
and voltages that are calculated over a cycle. A short tripping time is hereby 
achieved. It is therefore well suited in system applications where short tripping times 
are more desired than high accuracy of real power.
Pickup Seal-In Time To ensure that frequently occurring short pickups can cause tripping, a selectable pro-
longation of these pickup signals is provided. Should new fault detection signals 
appear within this seal-in time the pickup is maintained, so that a delayed tripping can 
take place.
Delay and Logic Two delay times are available for the delay of the trip command.
When used as a reverse power protection for generators, bridging a perhaps short 
power input during synchronisation or during power swings caused by system faults, 
the trip command is delayed by a selectable time T-SV-OPEN. In case of a closed