1 Introduction
28
7UT613/63x Manual
C53000-G1176-C160-2
User-defined Logic
Functions (CFC)
Freely programmable combination of internal and external signals for the imple-
mentation of user-defined logic functions
All usual logic functions
Time delays and limit value inquiries
Commissioning,
Operation
Isolation of one side or measuring point for maintenance work: the isolated line or
measuring point is withdrawn from the differential protection system processing,
without affecting the remainder of the protection system
Comprehensive support facilities for operation and commissioning
Indication of all measured values, amplitudes and phase relation
Indication of the calculated differential and restraint currents
Integrated help tools can be visualised by means of a standard browser: Phasor di-
agrams of all currents of all sides and measuring locations of the protected object
are displayed as a graph.
Connection and direction checks as well as interface check
Monitoring Func-
tions
Availability of the device is greatly increased because of self-monitoring of the inter-
nal measurement circuits, power supply, hardware, and software
Supervision of the current transformer secondary circuits of symmetry and phase
sequence
Monitoring of the voltage transformer circuits (if voltage inputs are available) for
symmetry, voltage sum and phase rotation
Supervision of the voltage transformer circuits (if voltage inputs are available) for
voltage failure with fast function blocking that measure undervoltages
Checking the consistency of protection settings regarding the protected object and
possible assignment of the current inputs: Blocking of the differential protection
system in case of inconsistent settings which could lead to a malfunction
Trip circuit supervision is possible.
Broken wire supervision for the secondary CT circuits with fast phase segregated
blocking of the differential protection functions and the unbalanced load protection
in order to avoid spurious tripping.
Further Functions Battery-buffered real-time clock, which may be synchronised via a synchronisation
signal (e.g. DCF77, IRIG B via satellite receiver), binary input or system interface
Continuous calculation and display of operational measured values on the front of
the device; indication of measured quantities of all sides of the protected object
Fault event memory (trip log) for the last 8 network faults (faults in the power sys-
tem), with real-time assignment
Fault recording memory and transmission of the data for analogue and user-defined
binary signals with a maximum time range of about 5s
Switching Statistics: Recording of the trip commands issued by the device, as well
as recording of the fault current data and accumulation of the interrupted fault cur-
rents