4.13 Forward active power supervision
473
7UT613/63x Manual
C53000-G1176-C160-2
Influencing Variables for Pickup Values
Power supply direct voltage in range 
0.8 ≤ U
H
/U
HN
 ≤ 1,15
≤ 1 %
Temperature in range 
–5 °C ≤ Θ 
amb
 ≤ 55 °C
≤ 0.5 %/10 K
Frequency in range 0.95 ≤ f/f
N
 ≤ 1.05 ≤ 1 %
Harmonics 
- up to 10 % 3rd harmonic 
- up to 10 % 5th harmonic
 
≤ 1 %
≤ 1 %