A.4 Current Transformer Requirements
541
7UT613/63x Manual
C53000-G1176-C160-2
Mismatching factor for 7UT613/63x, (limited resolution of the measurement)
Caution
: If earth fault differential protection is used, the requirement for the phase
current transformer of the REF side is as follows:
1
/
4
F
Adap
4, (for the starpoint trans-
former remains
1
/
8
F
Adap
8)
Figure A-30 CT verification for Devices 7UT613/63x
The CB layout within the power station unit is not specified.
where:
I
nO
= rated current of the protected object
(in relation to the parameterised rated current)
U
nO
= parameterised rated current of the protected object
I
Nrelay
= nominal device current
S
Nmax
= maximum (rated) power of the protected object
(for transformers: side with the largest (rated) load)
x”
d
= sub-transient direct-axis reactance of the generator in p.u.
U
k
= transformer short-circuit voltage HV - LV in %
R
relay
= assumed with 0.1 , (the consumption of the above devices is below
0.1 VA)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT63 series and is the answer not in the manual?

Siemens SIPROTEC 7UT63 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT63 series
CategoryProtection Device
LanguageEnglish

Related product manuals