C53000-G1176-C160-2
576 Primary fault current IL1 side1
(IL1S1:)
P.System Data 2 VI * *
577 Primary fault current IL2 side1
(IL2S1:)
P.System Data 2 VI * *
578 Primary fault current IL3 side1
(IL3S1:)
P.System Data 2 VI * *
579 Primary fault current IL1 side2
(IL1S2:)
P.System Data 2 VI * *
580 Primary fault current IL2 side2
(IL2S2:)
P.System Data 2 VI * *
581 Primary fault current IL3 side2
(IL3S2:)
P.System Data 2 VI * *
582 Primary fault current I1 (I1:) P.System Data 2 VI * *
583 Primary fault current I2 (I2:) P.System Data 2 VI * *
584 Primary fault current I3 (I3:) P.System Data 2 VI * *
585 Primary fault current I4 (I4:) P.System Data 2 VI * *
586 Primary fault current I5 (I5:) P.System Data 2 VI * *
587 Primary fault current I6 (I6:) P.System Data 2 VI * *
588 Primary fault current I7 (I7:) P.System Data 2 VI * *
916 Increment of active energy
(Wp=)
Energy -
917 Increment of reactive energy
(Wq=)
Energy -
1000 Number of breaker TRIP com-
mands (# TRIPs=)
Statistics VI
1020 Counter of operating hours
(Op.Hours=)
Statistics VI
4523 >Block external trip 1 (>BLOCK
Ext 1)
External Trips SP * * * LED BI BO
4526 >Trigger external trip 1 (>Ext trip
1)
External Trips SP ON
OFF
* * LED BI BO 51 126 1 Yes
4531 External trip 1 is switched OFF
(Ext 1 OFF)
External Trips OUT ON
OFF
* * LED BO 51 131 1 Yes
4532 External trip 1 is BLOCKED (Ext
1 BLOCKED)
External Trips OUT ON
OFF
ON
OFF
* LED BO 51 132 1 Yes
4533 External trip 1 is ACTIVE (Ext 1
ACTIVE)
External Trips OUT ON
OFF
* * LED BO 51 133 1 Yes
4536 External trip 1: General picked up
(Ext 1 picked up)
External Trips OUT * ON
OFF
* LED BO 51 136 2 Yes
4537 External trip 1: General TRIP (Ext
1 Gen. TRIP)
External Trips OUT * ON * LED BO 51 137 2 Yes
4543 >BLOCK external trip 2 (>BLOCK
Ext 2)
External Trips SP * * * LED BI BO
4546 >Trigger external trip 2 (>Ext trip
2)
External Trips SP ON
OFF
* * LED BI BO 51 146 1 Yes
4551 External trip 2 is switched OFF
(Ext 2 OFF)
External Trips OUT ON
OFF
* * LED BO 51 151 1 Yes
4552 External trip 2 is BLOCKED (Ext
2 BLOCKED)
External Trips OUT ON
OFF
ON
OFF
* LED BO 51 152 1 Yes
4553 External trip 2 is ACTIVE (Ext 2
ACTIVE)
External Trips OUT ON
OFF
* * LED BO 51 153 1 Yes
4556 External trip 2: General picked up
(Ext 2 picked up)
External Trips OUT * ON
OFF
* LED BO 51 156 2 Yes
4557 External trip 2: General TRIP (Ext
2 Gen. TRIP)
External Trips OUT * ON * LED BO 51 157 2 Yes
No. Description Function
Type of Information
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log On/Off
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation