2.1 General
77
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-16 Polarity check for 1-phase current inputs IX1
The following applies for the (max. 4, dependent on device version on connections)
1-phase current inputs:
For the auxiliary measuring input X1
• Address 711 EARTH IX1 AT with the options Terminal Q7 or Terminal Q8,
• Address 712 IN-PRI CT IX1 = primary rated CT current,
• Address 713 IN-SEC CT IX1 = secondary rated CT current.
For the auxiliary measuring input X2
• Address 721 EARTH IX2 AT with the options Terminal N7 or Terminal N8,
• Address 722 IN-PRI CT IX2 = primary rated CT current,
• Address 723 IN-SEC CT IX2 = secondary rated CT current.
For the auxiliary measuring input X3
• Address 731 EARTH IX3 AT with the options Terminal R7 or Terminal R8
(not for high-sensitivity input),
• Address 732 IN-PRI CT IX3 = primary rated CT current,
• Address 733 IN-SEC CT IX3 = sec. rated CT current (not for high-sensitivity
input),
• Address 734 FACTOR CT IX3 = CT transform. ratio (only for high-sensitivity input).
For the auxiliary measuring input X4
• Address 741 EARTH IX4 AT with the options Terminal P7 or Terminal P8
(not for high-sensitivity input),
• Address 742 IN-PRI CT IX4 = primary rated CT current,
• Address 743 IN-SEC CT IX4 = sec. rated CT current (not for high-sensitivity
input),
• Address 744 FACTOR CT IX4 = CT transform. ratio (only for high-sensitivity input).
Note
For devices in panel surface mounted housing, terminal designations apply as per
table 2-4.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT63 series and is the answer not in the manual?

Siemens SIPROTEC 7UT63 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT63 series
CategoryProtection Device
LanguageEnglish

Related product manuals