2.1 General
85
7UT613/63x Manual
C53000-G1176-C160-2
216 NUMBER OF ENDS 3
4
5
6
7
8
9
10
11
12
6 Number of Ends for 1 Phase
Busbar
220 ASSIGNM. 2M,2S M1,M2 M1,M2 Assignment at 2 assig.Meas.Loc./
2 Sides
221 ASSIGNM. 3M,2S M1+M2,M3
M1,M2+M3
M1+M2,M3 Assignment at 3 assig.Meas.Loc./
2 Sides
222 ASSIGNM. 3M,3S M1,M2,M3 M1,M2,M3 Assignment at 3 assig.Meas.Loc./
3 Sides
223 ASSIGNM. 4M,2S M1+M2,M3+M4
M1+M2+M3,M4
M1,M2+M3+M4
M1+M2,M3+M4 Assignment at 4 assig.Meas.Loc./
2 Sides
224 ASSIGNM. 4M,3S M1+M2,M3,M4
M1,M2+M3,M4
M1,M2,M3+M4
M1+M2,M3,M4 Assignment at 4 assig.Meas.Loc./
3 Sides
225 ASSIGNM. 4M,4S M1,M2,M3,M4 M1,M2,M3,M4 Assignment at 4 assig.Meas.Loc./
4 Sides
226 ASSIGNM. 5M,2S M1+M2+M3,M4+M5
M1+M2,M3+M4+M5
M1+M2+M3+M4,M5
M1,M2+M3+M4+M5
M1+M2+M3,M4+M5 Assignment at 5 assig.Meas.Loc./
2 Sides
227 ASSIGNM. 5M,3S M1+M2,M3+M4,M5
M1+M2,M3,M4+M5
M1,M2+M3,M4+M5
M1+M2+M3,M4,M5
M1,M2+M3+M4,M5
M1,M2,M3+M4+M5
M1+M2,M3+M4,M5 Assignment at 5 assig.Meas.Loc./
3 Sides
228 ASSIGNM. 5M,4S M1+M2,M3,M4,M5
M1,M2+M3,M4,M5
M1,M2,M3+M4,M5
M1,M2,M3,M4+M5
M1+M2,M3,M4,M5 Assignment at 5 assig.Meas.Loc./
4 Sides
229 ASSIGNM. 5M,5S M1,M2,M3,M4,M5 M1,M2,M3,M4,M5 Assignment at 5 assig.Meas.Loc./
5 Sides
230 ASSIGNM. ERROR No AssigMeasLoc
No of sides
without Assignment Error
241 SIDE 1 auto-connected auto-connected Side 1 is assigned to
242 SIDE 2 auto-connected auto-connected Side 2 is assigned to
243 SIDE 3 auto-connected
compensation
earth.electrode
auto-connected Side 3 is assigned to
244 SIDE 4 auto-connected
compensation
earth.electrode
compensation Side 4 is assigned to
Addr. Parameter Setting Options Default Setting Comments