SIRIUS 3RV2 motor starter protectors
4.10 Technical data
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
475
Connection data for 3RV29 28-1H terminal blocks
Table 4- 36 Connection data for 3RV29 28-1H terminal blocks
Type 3RV29 28-1H
Specified tightening torque Nm 2.5 to 3
Conductor cross-sections
Front clamping point connected
Solid
mm² 1 to 10
Finely stranded with end sleeve
mm² 1 to 16
Stranded
mm² 2.5 to 25
AWG cables, solid or stranded
mm² 14 to 3
Connection screw M4
Rear clamping point connected
Solid
mm² 1 ... 10
Finely stranded with end sleeve
mm² 1 to 16
Stranded
mm² 1.5 ... 25
AWG cables, solid or stranded
mm² 16 to 3
Connection screw M4
Both clamping points connected
Front clamping point:
- Solid mm² 1 to 10
- Finely stranded with end sleeve mm² 1 to 10
- Stranded mm² 2.5 to 10
- AWG cables, solid or stranded mm² 14 to 6
- Connection screw M4
Rear clamping point:
- Solid mm² 1 to 10
- Finely stranded with end sleeve mm² 1 to 10
- Stranded mm² 5 ... 25
- AWG cables, solid or stranded mm² 16 to 3
- Connection screw M4
Reference
More information about accessories is available in the chapter titled Phase barriers/UL 508
"type E" terminals (Page 422).