SIRIUS 3RA28 function modules for mounting on 3RT2 contactors
7.5 Configuration
SIRIUS Innovations
658 System Manual, 01/2011, A8E56203870002-03
3RA2815-..W10
L1(+)
N(-)
S1
A2
A1
16
18
15
Q
200 ms
A
1/A2
15/18
15/16
t
L1(+)
N(-)
S1
A2
A1
36
28
27 35
Q
200 ms
A
1/A2
27/28
35/36
t
The 3RA2815 solid-state time-delay auxiliary switch has the following features:
The voltage is supplied through the plug-in contacts directly via the contactor's coil
terminals, parallel to A1/A2.
The timing function is activated by switching on the contactor on which the delayed
auxiliary switch is mounted.
The 3RA2815 solid-state time-delay auxiliary switch works without auxiliary voltage.
The minimum ON duration is 200 ms.
A varistor is integrated in the solid-state time-delay auxiliary switch to attenuate contactor
coil switching overvoltages.
Note
The setting of the output contacts is not defined in as-supplied state (bistable relay).
Connect the control voltage and then disconnect it again to set the contacts to the normal
position.