SIRIUS 3RR2 current monitoring relays
8.10 Technical data
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
739
Type 3RR2141 3RR2142
Size S00 S0
Width 45 mm 45 mm
Electromagnetic compatibility (EMC) - Immunity
ï‚· Conducted interference suppression
- Burst acc. to IEC 61000-4-4
(corresponds to severity 3)
kV 2 (power ports), 1 (signal ports)
- Surge acc. to IEC 61000-4-5
(corresponds to severity 3)
kV 2 (line to ground), 1 (line to line)
ï‚· Electrostatic discharge acc. to
IEC 61000-4-2
(corresponds to severity 3)
kV 8 (air discharge), 6 (contact discharge)
ï‚· Field-related interference suppression to
IEC 61000-4-3
(corresponds to severity 3)
V/m 10
Electromagnetic compatibility (EMC)
– Emitted interference
acc. to EN 55011 (CISPR 11) and EN 55022
(CISPR 22)
Limit class A (Industry)
Mech. operating cycles 10.000.000
Electr. operating cycles at AC-15/230 V 100.000
Dimensions See Dimension drawings (dimensions in mm) (Page 750)
Installation altitude above sea level m Up to 2,000; above this, please contact us
Mounting position Any
Type of fixing Direct mounting/stand-alone assembly with terminal support

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIRIUS 3RF Series and is the answer not in the manual?

Siemens SIRIUS 3RF Series Specifications

General IconGeneral
BrandSiemens
ModelSIRIUS 3RF Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals