Technical data
13.3 Expansion modules
3SK1 safety relays
Manual, 04/2013, A5E02526190021A/RS-AA/01
233
13.3.1.2 Technical data for output expansion 3SK1213
3SK1213-.AB.. 3SK1213-.AJ.. 3SK1213-.AL..
Insulation voltage rated value V 300
Resistance against shock 5 g / 10 ms
Number of sensor inputs 1-channel
or 2-channel
—
Type of the safety-related wiring of
the inputs
—
Product feature transverse contact-
secure
—
Safety Integrity Level (SIL)
according to IEC 61508
SIL3
SIL claim limit (for a subsystem)
according to EN 62061
3
Performance level (PL) according to
ISO 13849-1
e
Category according to ISO 13849-1 4
T1 value for proof test interval or
service life according to IEC 61508
a 20
Safety device type according to
IEC 61508-2
Type A
Number of outputs as contact-
affected switching element
• as NC contact for reporting
function instantaneous switching
0
• as NO contact for reporting
function instantaneous switching
0
• as NC contact for reporting
function delayed switching
0
• as NO contact for reporting
function delayed switching
0
• as NC contact safety-related
instantaneous switching
0
• as NO contact safety-related
instantaneous switching
3
• as NC contact safety-related
delayed switching
0
• as NO contact safety-related
delayed switching
0
Stop category according to
DIN EN 60204-1
0
Design of the input start input —
Design of the electrical connection
jumper socket
No