Setup with the integrated HMI
7.3Menu overview
Menu item Parameter Setting Default
VFLOW UNITS = Level
Scaling: ScalingUnit
l/s, l/min, l/h, MI/d, m
3
/s, m
3
/min, m
3
/h, m
3
/
d, lb/s, lb/min, lb/h, gal/s, gal/min, gal/h,
gal/d, Mgal/d, ft
3
/s, ft
3
/min, ft
3
/h, ft
3
/d, bbl/
s, bbl/min, bbl/h, bbl/d, ImpGal/s, ImpGal/
min, Imp/Gal/h, ImpGal/d
l/s
SCALE FORMAT Level Scaling: Decimal Places Display 0
UPPER SCALNG Level Scaling: Max Scaled Value 100l/s
AFES RANGE Distance 00000AFES
CONFIRM
Menu item Parameter Setting Default
LEVEL Level
SPACE Space
DIST Distance
VOL Scaled value
VFLOW Scaled value
CONF Measurement reliability
DISTSELECTION = Hart
Dynamic Variable
Channel: Device Variable
Code For SV
STEMP Transmitter temperature
LINR Linear
CYLIN Horizontal cylindrical vessel
VENTU Venturi-, trapezoidal weir,
rectangle weir
PALM Flow Palmer-Bowlus flume
V-NOT Flow VNotch-, triangle weir
CONIC Conical Bottom
SELECT
OUTPUT
LINEARIZTYPE =
Linearization Curve Type
FLAT Inclined Bottom
Linear
SENSOR UNITS = Device Units:
Physical Value Unit
mm, m, in, ft m
LOWER CAL PT Level Adjustment Data 15m
UPPER CAL PT Level Adjustment Data 0m
CALIBRATION
SENSR OFFSET Offset Application Value 0m
LOOP CUR MDE =
Display_Read Write Hart
Parameter. Loop Current
Mode
ON = Enabled (4…20mA)
OFF = Disabled (4mA fixed)
ON
DAMPING =
Level_Integration Time.
Responsetime
0…999s 0s
OUT CHARACT = Main
Current Output_
Configuration: Gradient
Type
4…20mA = rising gradient, 20…4mA =
falling gradient
4…20mA
CURRENT OUT
SATURATE CUR
= Main Current
Output_Configuration:
Current Limits
3.8…20.5mA, 4…20mA 3.8…20.5mA
SITRANS LR150
Operating Instructions, 08/2020, A5E50352155
31