Setup with the integrated HMI
7.9Communication
7.9 Communication
7.9.1 HART address
Function
POLLING ADR:
Sets the device address in a HART network.
For point-to-point configurations the standard address is zero (0).
For multidrop configurations, use a non-zero HART address, i.e. 1 to 63.
7.10 Safety
7.10.1 user PIN
Is used to activate/deactivate the user PIN. If the user PIN is activated, a PIN must be
entered when changing parameter settings.
Note
The device is unlocked on delivery.
A change of the setting for parameter " User PIN" does not take effect
immediately. After changing the setting, the device must be restarted or ten (10)
minutes must elapse before the change takes effect.
Setting Selection Selection Description
ACTIVT Activate User PIN
Display = OK
USER PIN USER PIN
CANCL Deactivate User PIN
Display = ENABL
7.10.2 Bluetooth PIN
BLUETOOTH PIN:
In this menu item, you can change the factory-preset Bluetooth access code to your
personal Bluetooth access code.
Note
The individual preset Bluetooth access code of the device can be found on the
supplied information sheet " Device Bluetooth and Parameter Access Codes". If this
SITRANS LR150
Operating Instructions, 08/2020, A5E50352155
61