Diagnostics and troubleshooting
12.4Status messages according to NE107
more detailed error messages available under the menu item " Diagnostics" via
the respective adjustment module.
Status messages
The status messages are divided into the following categories:
• Failure
• Function check
• Out of specification
• Maintenance required
and explained by pictographs:
1
Failure - red
2
Out of specification - yellow
3
Function check - orange
4
Maintenance required - blue
Figure12.1 Pictographs of the status messages
Failure: Due to a malfunction in the transmitter, a fault message is output.
This status message is always active. It cannot be deactivated by the user.
Function check: The transmitter is being worked on, the measured value is
temporarily invalid (for example during simulation).
This status message is inactive by default.
Out of specification: The measured value is unreliable because an transmitter
specification was exceeded (e.g. electronics temperature).
This status message is inactive by default.
Maintenance required: Due to external influences, the transmitter function is
limited. The measurement is affected, but the measured value is still valid. Plan in
maintenance for the transmitter because a failure is expected in the near future (e.g.
due to buildup).
This status message is inactive by default.
Failure
Code
Text message
Cause Rectification DevSpec
State in CMD 48
F013 No measured value in the
switch-on phase or during
operation
Check or correct installation
and/or parameter settings
Byte5, Bit0 of
Byte0…5
SITRANS LR150
Operating Instructions, 08/2020, A5E50352155
77