Connections
37
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
7.6.1 Monitored control output 1
This output is exclusively reserved for the connection of the Sounders. Operation is
defined at programming steps 05 and 10 (see paragraphs 12.4 and 12.6).
Fig. 22 XC100x-A, monitored control output 1 connection
1 Sounders
2 Control output not used (no EOL required)
7.6.2 Monitored control output 2
This output can be used for several purposes. Operation is defined at programming
step 11 (see paragraph 12.6).
Fig. 23 XC100x-A, monitored control output 2 connection
1 RT-alarm
2 Fire control(s): signal triggering to equipment outside the system, according to
EN12094-1 option with requirements 4.26
3 Sounder(s)
4 Warning panel(s) « Mechanical blocked » or « Automatic or manual blocked »
or « Automatic and manual blocked »
5 Control output not used (no EOL required)