Maintenance
82
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
14.2 Detailed fault display
Press simultaneously keys “1” and “3” of the numeric keypad:
è Faults appear for 10 seconds according to the table below
OL: Open Line
SC: Short Circuit
System ON
Silence
buzzer
Silence
Re-sound
Sounders
Automatic blocked
Activated
Mode
Operating access
Earth fault
System fault
Disable
Fault
Manual blocked
Manual release
Released
Detector Zone 1
………………………………….
Mechanical blocked
Loss of agent
Incorrect status
Emergency
hold
Sounders
Fire controls
Disable
Enable
Detector test
Fire alarm
Remote transmission
Disable
Test
Enable
Detector Zone 2
……………………………………
Detector Zone 3
……………………………………
432
1
5 2
1
2
4
5
6
7
8
9
10 19
21
11
12
13
14
15
16
17
24
26
28
30
32
25
27
29
31
8
10
12
13
9
6
7 14
15
Disable
Test
Enable
Disable
Test
Enable
Disable
Test
Enable
3
18
Power supply
Reset
RT-fault
RT-alarm
22
23
11
20
Actuators
Led test
Disable
Enable
LED
Designation State Significance
N° Color
2 Yellow Fault Fixed Multi-sector function: individual module (XCA1030) disconnected
Slow Multi-sector function: RS485 bus (OL / SC / communication fault)
3 Yellow Power supply fault Fixed Multi-sector function: loss of agent
Slow Multi-sector function: loss of agent (OL / SC)
5 Yellow Earth fault Fixed Multi-sector function: earth fault
6 Yellow Disable Fixed Multi-sector function: actuator (OL / SC)
Slow Multi-sector function: inter-blocking (OL / SC)
Fast Multi-sector function: actuator + inter-blocking (OL / SC)
7 Yellow Test Fixed Multi-sector function: selector valve (SC)
Slow Multi-sector function: selector valve (OL)
Fast Multi-sector function: selector valve (incorrect status)
8 Red Fire alarm Fixed Multi-sector function: actuator blocked
9 Red Remote transmission Fixed Multi-sector function: power supply fault
11 Yellow Mechanical blocked Fixed SC Monitored input 1
Slow OL
12 Yellow Incorrect status Fixed SC Monitored input 2
Slow OL
13 Yellow Loss of agent Fixed SC Monitored input 3
Slow OL
Fast Incorrect status
14 Yellow Manual blocked Fixed SC Monitored input 4
Slow OL
15 Yellow Not used Fixed 24 V output fuse blown
16 Yellow Automatic blocked Fixed Key enabled more than 5 mn
19 Yellow Sounders Fixed SC Monitored output 1
Slow OL