Programming
67
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
30 Processing as “Sounders” (see steps 05 and 10 and paragraph 12.1)
31 Active in state "Selector valve opened" (XCA1030 multi-sector module)
32 Active in state "Extinguishing activated from electrical manual release"
33 Active in state "Extinguishing activated from automatic detectors"
34 Active in state "Extinguishing activated from remote activation"
35 Active in state "Fault" condition
36 Active in state of LED test
37 Processing as “Door holder” inverted
38 Combined option 17 and option 11
16 Relay contact 2 : select the function
Same options as relay contact 1 – default = 01
17 Relay contact 3 : select the function
01 Processing as "RT-fault"
18 Relay contact 4 : select the function
Same options as relay contact 1 – default = 12
19 Relay contact 5 : select the function
Same options as relay contact 1 – default = 16
12.8 Steps 20 to 27 - Driver outputs 1 to 8
Description
20 Driver output 1 : select the function
01 Processing as “Fire controls A” (see paragraph 12.1)
02 Processing as “Fire controls B” (see paragraph 12.1)
03 Processing as “Fire controls C” (see paragraph 12.1)
04 Active in state ”Fire alarm” until “Reset”
05 Active in state ”Activated” until “Reset”
06 Active in state ”Released” until “Reset”
07 Active in state “Fire alarm” or “Activated” or ”Released” until “Reset”
08 Active in state “Activated” or ”Released” until “Reset” (same as option 05)
09 Active in state “Loss of agent”
10 Active in state “Detector test”
11 Active in state “Disabled”
12 Active in state “Emergency hold/abort”
13 Active in state “Mechanical blocked”
14 Active in state “Automatic blocked”
15 Active in state “Manual blocked”
16 Active in state “Automatic blocked” or “Manual blocked”
17 Active in state “Automatic blocked” and “Manual blocked”
18 Inactive in state “Pre-activated” or “Activated” or “Released”
Active in all other condition
Application : use of a fail safe door magnetic solenoid
19 Inactive in state "Normal" with operating access level 1 only
Active in all other states
Application: the customer needs a remote indication as soon as the panel is not anymore in a "Standby" condition and as
soon as somebody is operating the panel
20 Inactive in state "Normal" with operating access level 1 or 2
Active in all other states
Application: the customer needs a remote indication as soon as the panel is not anymore in a "Standby" condition
21 Active during 5 seconds when the key reset is pressed
Application: reset of an XC10 panel and reset of an ASD system within a single operation