Programming
76
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
68 100 seconds
69 105 seconds
70 110 seconds
71 115 seconds
72 120 seconds
99 Same as pre-discharged warning time of automatic release
66 Configure Manual Release “pre-discharge” warning time to overwrite Automatic release “pre-discharge” warning time
01 Manual release “pre-discharge” warning time does not overwrite Automatic release “pre-discharge” warning time
02 Shorter Manual release “pre-discharge” warning time overwrite longer Automatic release “pre-discharge” warning time
03 Following an automatic triggering signal, manual release overwrite emergency hold/abort (NFPA2001 compliant, EN12094-1
not compliant)
12.22 Step 67 – Operation if “Discharge” is activated in standby
67 Operation in case "Discharge contact" activated during standby condition
01 Actuators outputs are activated (concern XC10 lines 4 and 5, XCA1031 lines 1 and 2)
Note: cannot be used with Step8_Option4!!
02 Actuators outputs are not activated (concern XC10 lines 4 and 5, XCA1031 lines 1 and 2)
Application: for AT only