Programming
74
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
07 7
08 8
09 9
10 10
11 11
12 12
13 13
14 14
15 15
16 16
61 Configure Repeater silence buzzer
01 Silence buzzer on XC10 do not silence buzzer on repeater terminal
02 Silence buzzer on XC10 silences buzzer on repeater terminal
12.19 Step 62 - Loss of agent in multi-sector application
Description
62 XCA1031 loss of agent contact programming
01 Contact (1.2 kΩ) normally closed when cylinders pressure/weight is correct
02 Contact (1.2 kΩ) normally opened when cylinders pressure/weight is correct
12.20 Steps 63 to 64 - Fire damper
Description
This output is used to connect a fire damper that must be that must be opened a few seconds before the gas release and closed once the
gas is released. For safety reasons, it is not recommanded to connect an over-pressure flap to this output (In case the line is broken,
damage may occur on the room structure).
63 Select start of activation
Example: if the configured “Pre-discharged warning time” is 30s, options 02..03 are automatically reduced to 30s
01 Activated at the beginning of the “Pre-discharged warning time”
02 Activated 50s before the end of the “Pre-discharged warning time”
03 Activated 40s before the end of the “Pre-discharged warning time”
04 Activated 30s before the end of the “Pre-discharged warning time”
05 Activated 20s before the end of the “Pre-discharged warning time”
06 Activated 10s before the end of the “Pre-discharged warning time”
07 Activated at the end of the “Pre-discharged warning time”
64
Select the activation duration after the end of the “Pre-discharged warning time"
01 0 second
02 2 seconds
03 4 seconds
04 6 seconds
05 8 seconds
06 10 seconds
07 15 seconds
08 20 seconds
09 25 seconds
10 30 seconds
11 35 seconds
12 40 seconds
13 45 seconds