Multi-sector installation
49
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
8.4 Modules technical specification
XCA1030:
Selector valve position monitoring input:
- line monitoring: 3.3 kΩ resistance connected at the end of the line
- contact resistor: 1.2 kΩ
- line resistance: 80 Ω max.
XCA1031:
Actuator line 1 and 2:
- device can be either electromagnetic or pyrotechnic actuator
- activation by reverse polarity (polarities indicated are “activated” polarities,
according to connected device, a diode can be necessary)
- line monitoring: 3.3 kΩ resistance connected at the end of the line
- protection: 1 AF fuse (F1 / F2)
- cable type: 2 x 2.5mm
2
max.
- length / resistance of the line: see paragraph 7.6
Loss of agent input:
- line monitoring: 3.3 kΩ resistance connected at the end of the line
- contact resistor: 1.2 k Ω
- line resistance: 80 Ω max.
See paragraph 14.2 for detailed display of faults and states related to multi-sector application.
See paragraph 8.3 for assembly and connection details.