Programming
75
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
14 50 seconds
15 55 seconds
16 1 minute
17 1 mn 10 s
18 1 mn 20 s
19 1 mn 30 s
20 1 mn 40 s
21 1 mn 50 s
22 2 mn
23 2 mn 10 s
24 2 mn 20 s
25 2 mn 30 s
26 2 mn 40 s
27 2 mn 50 s
28 3 mn
29 3 mn 30 s
30 4 mn
31 4 mn 30 s
32 5 mn
33 Until “Reset”
12.21 Step 65 to 66 - Pre-discharged warning time in manual release
Description
65 Configure a different pre-discharged warning time in case of manual release (typically less than pre-discharged time of
automatic release)
The Pre-discharged warning time sets the countdown duration before the actuator extinguishing release triggering. During this time,
the reset function is not possible. Adjustable from 0 to 120 seconds by step of 5 seconds
Default : 30 s
Values from 65 seconds to 120 seconds are not compliant to EN12094-1. This must be clearly indicated in the installation test
report. (Application: activate dampers during the pre-discharged warning time, which need 100 - 120 seconds to open)
00 0 second
05 5 seconds
10 10 seconds
15 15 seconds
20 20 seconds
25 25 seconds
30 30 seconds
35 35 seconds
40 40 seconds
45 45 seconds
50 50 seconds
55 55 seconds
60 60 seconds
61 65 seconds
62 70 seconds
63 75 seconds
64 80 seconds
65 85 seconds
66 90 seconds
67 95 seconds