Operating access levels
56
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
10 Operating access levels
XC100x-A equipment operation is organised in several operating access levels.
10.1 Operating access level 1
This level gives access to:
- silence buzzer (see programming options in step 56)
- led test
- fault detailed display
- alarm counter display (XC1003-A and XC1005-A only)
10.2 Operating access level 2
This operating access level gives access, after code input on keyboard (4 2 3 3 by
default or personalised) or by key (option), to the following controls:
- silence buzzer (see programming options in step 56)
- silence / re-sound sounders
- automatic blocked / automatic and manual blocked
- disable / enable
- test of zones 1...4
- reset
- test of sounders, warning panels, RT-alarm and RT-fault
- Operating access level 2 is automatically disabled after 4 minutes if no handling is carried out for
this period
- Operating access level 2 can be manually swiched back to level 1 after the same code input (For
customers who don't want to wait 4 minutes)
10.3 Operating access level 3A
This operating access level gives access, after code input on the keyboard, to the
“system test” function (see paragraph 15.6).
10.4 Operating access level 3B
This operating access level gives access, after removing the front plastic cover and
codes input on the keyboard, to:
- user functions programming
- outputs individual test
- checksum display
- alarm counter display
- maintenance PC connection (no code is needed)