Programming
70
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
09 Emergency hold -EN 12094-1 4.20.3 b) compliant
Contact (1.2 kΩ) opened during pre-discharged warning time = extinguishing process is hold as long as the contact is
maintained opened. When contact is released, pre-discharged warning time restarts
Contact (1.2 kΩ) opened after actuator activation = no effect
Contact (1.2 kΩ) opened at any other time = "Automatic blocked". Return back to “Normal” condition is possible only with
the “Mode” push buton or with external button connected to a control input configured with step 49. 51 option 13
Application: for RU only
12.10 Steps 32 to 38 - Reset
Step
O
p
tion
Description
32 Reset: zones 1 and 2 operation
01 Alarm < 15 seconds after reset = "Alarm"
02 Alarm < 15 seconds after reset = "Fault"
(If an alarm occurs in first 15secs after Reset, a fault will be raised (no matter in what condition the panel was before Reset).
33 Reset: zone 3 operation
01 Alarm < 15 seconds after reset = "Alarm"
02 Alarm < 15 seconds after reset = "Fault"
(If an alarm occurs in first 15secs after Reset, a fault will be raised (no matter in what condition the panel was before Reset).
34 Reset: manual control input operation
01 Input enabled < 15 seconds after reset = "Alarm"
02 Input enabled < 15 seconds after reset = "Fault"
(If a manual release occurs in first 15secs after Reset, a fault will be raised (no matter in what condition the panel was before
Reset).
35 Reset: monitored input 1 operation (discharged contact)
01 Input enabled < 15 seconds after reset = "Released"
02 Input enabled < 15 seconds after reset = "Fault"
(If a discharge contact activation occurs in first 15secs after Reset, a fault will be raised (no matter in what condition the panel
was before Reset).
36 Reset: front panel key operation
01 Reset possible only after:
è "Silence buzzer" and
è "Silence sounders" and
è "Flooding time"
02 Reset possible only after:
è "Silence buzzer" and
è "Silence sounders" and
è "Flooding time" and
è "Manual release" is reset and
è "Discharged" contact is reset
37 Reset: control input 1 operation
01 Reset possible at any time (not EN 12094-1 and EN 54-2 compliant)
02 Reset possible only after:
è "Silence buzzer" and
è "Silence sounders" and
è "Flooding time" and
è "Manual release" is reset and
è "Discharged" contact is reset
03 Reset possible only after flooding time
38 Reset during emergency hold
01 Reset is possible during "Emergency hold" (not EN 12094-1 compliant)
02 Reset is not possible during "Emergency hold"
12.11 Steps 39 to 43 - Operation
Step
O
p
tion
Description
39 Buzzer in state "Emergency hold/abort" operation

Table of Contents