Maintenance
83
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
System ON
Silence
buzzer
Silence
Re-sound
Sounders
Automatic blocked
Activated
Mode
Operating access
Earth fault
System fault
Disable
Fault
Manual blocked
Manual release
Released
Detector Zone 1
………………………………….
Mechanical blocked
Loss of agent
Incorrect status
Emergency
hold
Sounders
Fire controls
Disable
Enable
Detector test
Fire alarm
Remote transmission
Disable
Test
Enable
Detector Zone 2
……………………………………
Detector Zone 3
……………………………………
432
1
5 2
1
2
4
5
6
7
8
9
10 19
21
11
12
13
14
15
16
17
24
26
28
30
32
25
27
29
31
8
10
12
13
9
6
7 14
15
Disable
Test
Enable
Disable
Test
Enable
Disable
Test
Enable
3
18
Power supply
Reset
RT-fault
RT-alarm
22
23
11
20
Actuators
Led test
Disable
Enable
LED
Designation State Significance
N° Color
20 Yellow Actuators Fixed SC Monitored output 2
Slow OL
21 Yellow Fire controls Fixed SC Monitored output 3
Slow OL
22 Yellow RT-Fault Fixed SC Monitored output 4
Slow OL
Fast Calibration error
23 Yellow RT-Alarm Fixed SC Monitored output 5
Slow OL
Fast Calibration error
24 Yellow Emergency hold Fast Repeater error. Digit display indicates the first repeater in fault/missing
condition
25 Red Zone 1 Fixed Alarm < 15 s after reset Detection line 1
26 Yellow Zone 1 Fixed SC
Slow OL
27 Red Zone 2 Fixed Alarm < 15 s after reset Detection line 2
28 Yellow Zone 2 Fixed SC
Slow OL
29 Red Zone 3 Fixed Alarm < 15 s after reset Detection line 3
30 Yellow Zone 3 Fixed SC
Slow OL
31 Red Manual release Fixed Enabled < 15 s after reset Manual release line
32 Yellow Manual release Fixed SC
Slow OL
CAUTION
Any electrical fault (break or short circuit) on the following lines may have a
direct consequence on the extinguishing process, or in some cases prevent it.
- Detector lines
- Manual release line
- Monitored control output 1 to 5
- Monitored inputs 1 to 4
It is imperative to fix any fault in a short delay in order to not jeopardize an
extinguishing process.