SMA Solar Technology AG Parameter lists
Technical Description SI5048-TEN093630 157
235# Generator Start
Number Name Description Value Description Default
value
01 GnAutoEna Generator autostart Off Disable On
On Enable
02 GnAutoStr Number of autostarts 3
03 GnSocTm1Str SOC limit for switching
on generator for time 1
40 %
04 GnSocTm1Stp SOC limit for switching
off generator for time 1
80 %
05 GnSocTm2Str SOC limit for switching
on generator for time 2
40 %
06 GnSocTm2Stp SOC limit for switching
off generator for time 2
80 %
07 GnTm1Str Time 1 for generator
request in hh:mm:ss
Begin: Time 1,
End: Time 2
08 GnTm2Str Time 2 for generator
request in hh:mm:ss
Begin: Time 2,
End: Time 1
09 GnPwrEna Generator request
based on power
Off Disable Off
On Enable
10 GnPwrStr Generator request
switch-on power limit
4 kW
11 GnPwrStp Generator request
switch-off power limit
2 kW
12 GnPwrAvgTm Average time for
power-related
generator start
60 sec
13 GnTmOpEna Time-controlled
generator operation
Disable Enable Disable
Enable Disable
14 GnTmOpStrDt Starting date for time-
controlled generator
operation
2006.01.01
yyyy.mm.dd
15 GnTmOpStrTm Starting time for time-
controlled generator
operation in hh:mm:ss

Table of Contents