Parameter lists SMA Solar Technology AG
158 SI5048-TEN093630 Technical Description
236# CHP Control
16 GnTmOpRnDur Run time for time-
controlled generator
operation in hh:mm:ss
17 GnTmOpCyc Repeat cycle for time-
controlled generator
operation
Single One-time Single
Dayly daily
Weekly weekly
18 GnStrChrgMod Generator start for
charge type
Off off Both
Full Full charge
Equal Equalization
charge
Both Full- and
Equalization
charge
19 GnStrDigIn Generator start upon
signal of activated
digital input
Disable Enable Disable
Enable Disable
Number Name Description Value Description Default
value
01 ChpOpTmMin Minimum run time of
CHP plant
60 min
02 ChpStpTmMin Minimum stop time of
CHP plant
10 min
03 ChpPwrMax Maximum power of
CHP plant
5 W
04 ChpPwrMin Minimum power of CHP
plant
2 kW
05 ChpFrqPwrMax Maximum frequency of
CHP plant
51 Hz
06 ChpFrqPwrMin Minimum frequency of
CHP plant
52 Hz
07 ChpFrqOff 53 Hz
Number Name Description Value Description Default
value