SMA Solar Technology AG Parameter lists
Technical Description SI5048-TEN093630 159
237# CHP Start
Number Name Description displayed
value
Description Default
value
01 ChpSocTm1Str SOC limit for switching
on CHP plant for time 1
40 %
02 ChpSocTm1Stp SOC limit for switching
off CHP plant for time 1
80 %
03 ChpSocTm2Str SOC limit for switching
on CHP plant for time 2
40 %
04 ChpSocTm2Stp SOC limit for switching
off CHP plant for time 2
80 %
05 ChpTm1Str Time 1 for CHP plant
request in hh:mm:ss
Begin: Time 1,
End: Time 2
06 ChpTm2Str Time 2 for CHP plant
request in hh:mm:ss
Begin: Time 2,
End: Time 1
07 ChpPwrEna Activate CHP plant
request based on
power
Disable Enable Enable
Enable Disable
08 ChpPwrStr Generator request
switch-on power limit
4 kW
09 ChpPwrStrDly Time delay for power
request for CHP plant
5 min
10 ChpManStr Auto
Start
Stop
11 ChpAddOnTm Time for the additional
CHP request activated
60 sec
12 ChpAddOffTm Time for the additional
CHP request
deactivated
120 sec
13 ChpAddSocDel Distance to the next
SOC limit
5 %

Table of Contents