EasyManua.ls Logo

SMC Networks EX245-FPS1

SMC Networks EX245-FPS1
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 67 -
No.EX##-OMY0004
10.11.2.1. SW2
Not in use.
10.11.2.2. SW3
The two bits of the DIP-Switch “SW3are used for the commissioning mode (COMNG_MODE).
Table 10-29 SW3 details
Bit 1
Bit 2
Meaning
OFF
OFF
SM (Safety mode)
ON
OFF
Failure state
OFF
ON
Failure state
ON
ON
CM (Commissioning mode)
●The setting of the DIP switch SW3 is read during power-up. It is not permitted to change the settings
during normal operation as this may cause an error.
●The hardware configuration must include the correct ‘Safe digital I/Omodule. If the DIP switch is set
for SM (Safety mode) then use the ‘Safe digital I/O (SM)module. Alternatively if the DIP switch is set
for CM (Commissioning mode) then use the ‘Safe digital I/O (CM)module. Both modules are resident
in the Step7 or PCWorx hardware catalogue after the device GSDML (Step7/TIA) or FDCML (PCWorx)
file has been imported into it. Refer to Section: 8.1.1“GSD file and symbol filesfor details.
●“COMNG_MODEoccupies 1 byte for input data and 1 byte for output data.
●Diagnostics messages are supported.
●Parameters for safe-IOs are fixed in the firmware and are not adjustable
●F-Address should be in a parameter
Caution
In a production environment the SI unit must only be used in SM (Safety Mode)
IO mapping for the commissioning mode
IO Mapping for “COMNG_MODE”
Table 10-30 IO Mapping for “COMNG_MODE”
Byte
Meaning
INPUT
OUTPUT
0
Input data from safe inputs
Output data for safe outputs
Byte 0 of “COMNG_MODE”
Table 10-31 Byte 0 of “COMNG_MODE” details
Bit
Meaning
INPUT
OUTPUT
0
Input status of safe input 0
Safe power supply of US2 to the IO modules
1
Input status of safe input 1
Safe power supply of US2 to the valve zone 1
2
Input status of safe input 2
Safe power supply of US2 to the valve zone 2
3
Input status of safe input 3
Safe power supply of US2 to the valve zone 3
4
Input status of safe input 4
Reserved: Fixed 0
A non–zero value generates an error
5
Input status of safe input 5
6
Input status of safe input 6
7
Input status of safe input 7

Table of Contents

Related product manuals