Chapter 5 Display and Setting of Various Functions
HRSH Series 5.17 Pump Operation Mode Setting
5-41
5. Set circulating fluid discharge pressure with [▲] key or [▼] key, and press [SEL] key to
enter.
Table 5.17-3 Setting of circulating fluid discharge pressure
Set value
Explanation
Default
Setting and checking are not available when
it is set to frequancy set mode.
HRSH250/300-A
series,
HRSH100/150/200/
250-W-T
Other
models
Sets the circulating fluid discharge pressure.
Pressure setting unit for MPa: 0.01 MPa
Pressure setting unit for PSI: 1 PSI
HRSH250/300-A
series,
HRSH100/150/200/2
50-W-T
Other
models
MPa
to
to
PSI
to
to
*When SE.19 is set to "dI.2", the maximum value becomes 0.7MPa (102 PSI).
Setting: Pump operation frequency
6. Press the [SEL] key once.
Setting screen of the pump operation frequency appears on the digital display.
7. Set circulating fluid discharge pressure with [▲] key or [▼] key, and press [SEL] key to
enter.
Table 5.17-4 Setting of circulating fluid discharge pressure
Set value
Explanation
Default
Setting and checking are not available when it is
set to pressure control mode.
to
Sets the pump operation frequency.
*When SE.19 is set to "dI.2", the maximum value becomes 55Hz.
(Only HRSH250/300-A and HRSH100/150/200/250-W-T)
8. Press the [MENU] key once.
Returns to the main display (which shows the circulating fluid temperature).
PV
SV
PV
SV