Chapter 5 Display and Setting of Various Functions
5.20 Fan motor output upper limit setting HRSH Series
5-48
5.20.2 Setting/checking of the fan motor output upper limit
The table below shows the set item of the fan motor output upper limit and
the default setting.
Table5.20-2 Set item for fan motor output upper limit
Display
Item
Contents
Default
Fan motor output upper
limit setting
Set the motor output value.
HRSH100/150/200-A:60%
HRSH250-A:70%
HRSH300-A:100%(Unchangeable)
1. Press and hold the [MENU] key for approximately 2 seconds.
Repeat pressing the key until the key-lock setting screen [ ] appears on the digital
display.
Setting/checking:Fan motor output upper limit value
2. Press the [SEL] key 30 times.
Setting screen of Fan motor output upper limit setting appears on the digital display.
PV
SV
3. Select Fan motor output upper limit setting ON or OFF with [▲] key or [▼] key, and press [SEL]
key to enter.
Table5.20-3 Fan motor output upper limit setting
Model
Setting range
Default
HRSH100-A
HRSH150-A
HRSH200-A
HRSH250-A
HRSH300-A
-
*1
*1) The settings can not be changed for HRSH300-A.
4. Press the [MENU] key once.
Return to the main display (which shows the circulating fluid temperature).
PV
SV
PV
SV
PV
SV
PV
SV
Press and
hold [MENU]
key.
Press and
hold [MENU]
key.
Do not set the value lower than the setting range. Refrigerant
high pressure increases and the refrigerator becomes
overloaded, which affects the performance and life of this
product.