Chapter 5 Display and Setting of Various Functions
HRSH Series 5.22 Alarm Customizing Function
5-65
Setting/Checking: Monitoring start timer
32. Press the [SEL] key once.
Setting screen of the monitoring start timer is displayed on the digital display.
33. Set monitoring start timer with the [▲] key or the [▼] key, and press [SEL] key to enter.
Table 5.22-23 Setting of the monitoring start timer
Setting and checking are impossible when "0:
Continuous monitoring" or "1: Automatic
monitoring" is selected for the setting of AS21
"Temperature alarm monitoring method".
Sets the time when alarm monitoring starts.
Setting unit is 1 minute.
Settings of this function and example of alarm generating timing for 5.21.3 "Setting of
temperature alarm monitoring method and generation timing".
Setting/Checking: Range over detection timer
34. Press the [SEL] key once.
Setting screen of the range over detection timer is displayed on the digital display.
35. Set range over detection timer with the [▲] key or [▼] key, and press [SEL] key to enter.
Table 5.22-24 Setting of the range over detection timer
Sets time before the alarm is generated after the
alarm is generated.
Setting unit: 1 second
Settings of this function and example of alarm generating timing for 5.21.3 "Setting of
temperature alarm monitoring method and generation timing".