HRX-OM-Q026
Chapter 5 Display and Setting of Various Functions
HRSH Series 5.22 Alarm Customizing Function
5-69
Setting/Checking: Operation setting when "Circulating fluid discharge pressure sensor error" alarm is generated
38. Press the [SEL] key once.
Operation setting screen when "Circulating fluid discharge pressure sensor failure" alarm is
generated appears on the digital display.
39. Set the product operation when "Circulating fluid discharge pressure sensor failure"
alarm is generated with [▲] key or [▼] key, and press [SEL] key to enter.
Table 5.22-27 Operation setting when the "Circulating fluid discharge pressure sensor failure" alarm is generated
This alarm signal is not detected.
While this setting is ON, [ALARM] light on the
operation panel keeps blinking with the light ON for
0.5 seconds and OFF for 3 seconds.
Operation continues when this alarm is generated.
Operation stops when this alarm is generated.
Setting/Checking: Operation setting when "Pump maintenance" alarm is generated
40. Press the [SEL] key once.
Operation setting screen when "Pump maintenance" alarm is generated appears on the digital
display.
41. Set the product operation when "Pump maintenance" alarm is generated with [▲] key
or [▼] key, and press [SEL] key to enter.
Table 5.22-28 Operation setting when "Pump maintenance" alarm is generated
This alarm is not detected.
Operation continues when this alarm is generated.