HRX-OM-Q026
Chapter 3 Transport and Setting Up
3.4 Piping HRSH Series
3-30
Recommended piping circuit
Fig. 3-18 Recommended piping circuit
No. Description Size Recommended part no. Note
1 Valve Rc1/2 -
2 Valve Rc1 -
Y-strainer
Rc1
#40
Accessory
Filter
Rc1
20μm
HRS-PF005
Note)
4 Flow meter - -
Prepare a flow meter with an appropriate flow
range.
5
Valve
(Part of thermo-chiller)
Rc3/4 - -
Y-strainer
Rc1/2
#40
-
Filter
Rc1/2
20μm
-
7 Pressure gauge 0 to 1.0MPa - -
Y-strainer
Rc1
#40
HRS-S0212
Filter
Rc1
20μm
Refer to the table below
To prevent liquid spillage from the customer's
piping or overflow from the tank during
maintenance work.
3
Install either the strainer or filter. If foreign
objects with a size of 20 μm or more are likely to
enter, install the particle filter.
6
Install either the strainer or filter. If foreign
objects with a size of 20 μm or more are likely to
enter, install the particle filter.
8
Install either the strainer or filter. If foreign
objects with a size of 20 μm or more are likely to
enter, install the particle filter.
* Recommended filters for facility water inlet
Applicable model Recommended filter
HRSH100/150
FQ1012N-10-T020-B-X61 
Note)
HRSH200/250
FGESA-10-T020A-G2 
Note)
Note) The filter shown above cannot be directly connected to the
thermo-chiller. Install it in the user’s piping system.