HRX-OM-Q026
Chapter 3 Transport and Setting Up
3.4 Piping HRSH Series
3-30
◼ Recommended piping circuit
Fig. 3-18 Recommended piping circuit
No. Description Size Recommended part no. Note
1 Valve Rc1/2 -
2 Valve Rc1 -
Y-strainer
Rc1
#40
Accessory
Filter
Rc1
20μm
HRS-PF005
Note)
Prepare a flow meter with an appropriate flow
range.
Valve
(Part of thermo-chiller)
Rc3/4 - -
7 Pressure gauge 0 to 1.0MPa - -
Y-strainer
Rc1
#40
HRS-S0212
Filter
Rc1
20μm
Refer to the table below
To prevent liquid spillage from the customer's
piping or overflow from the tank during
maintenance work.
Install either the strainer or filter. If foreign
objects with a size of 20 μm or more are likely to
enter, install the particle filter.
Install either the strainer or filter. If foreign
objects with a size of 20 μm or more are likely to
enter, install the particle filter.
Install either the strainer or filter. If foreign
objects with a size of 20 μm or more are likely to
enter, install the particle filter.
* Recommended filters for facility water inlet
Applicable model Recommended filter
HRSH100/150
FQ1012N-10-T020-B-X61
Note)
Note) The filter shown above cannot be directly connected to the
thermo-chiller. Install it in the user’s piping system.