Chapter  3   Transport  and  Setting  Up 
 
3.5 Circulating Fluid Supply  HRSH Series 
 
  3-32 
◼  Ethylene glycol aqueous solution 
When ethylene glycol aqueous solution is used, prepare the ethylene glycol 
aqueous solution separately.   
Refer to "3.2.2 Operation at low ambient temperature or low circulating fluid 
temperature" for the concentration of the ethylene glycol aqueous solution. 
To control the concentration of the ethylene glycol aqueous solution, a 
densitometer is available (sold separately) from SMC. 
Ethylene glycol aqueous solution 60% 
Dilute to with clean water (tap 
water). 
Automatic water fill 
port 
Supply pressure: 0.2 to 0.5 MPa 
The piping should be ø25 mm or more and the length of 5 
meters or less. 
Avoid riser piping (trapping part). 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Fig. 3-20 Piping to the automatic water fill port and overflow port 
 
 
 
 
 
 
⚫ When using ethylene glycol aqueous solution, collect the 
overflowed fluid in the recycling pit and dispose it according to the 
local law of the country and area that the product is installed.   
⚫ When  using  ethylene  glycol  aqueous  solution,  check  the 
concentration periodically because the density will be reduced due 
to the automatic water fill function.