Chapter 5 Display and Setting of Various Functions
HRSH Series 5.8 Ready Completion (TEMP READY) Signal
5-21
5. Select READY bandwidth with [▲] key or [▼] key, and enter by pressing the [SEL] key.
Table 5.8-3 Set value for READY mode
Sets READY bandwidth (range between the upper and
lower limit temperatures) for the set circulating fluid
temperature.
Setting of READY bandwidth (range between the upper
and lower limit temperatures) for the set circulating fluid
temperature.
Setting temperature unit for Centigrade: 0.1
o
C
Setting temperature unit for Fahrenheit: 0.1
o
F
Setting/checking: READY time
6. Press the [SEL] key once.
Setting screen of READY time appears on the digital display.
7. Set READY time with [▲] key or [▼] key, and enter with the [SEL] key.
Table 5.8-4 Set value
Setting and checking are not available when
READY mode setting is OFF.
Sets time that is to maintain the set circulating fluid
temperature before starting the product
operation.Setting unit: 1 second
8. Press the [MENU] key once.
Returns to the main display (which shows the circulating fluid temperature).