Chapter  5   Display  and  Setting  of  Various  Functions 
 
5.21 Alarm Customizing Function  HRSH Series 
 
  5-64 
5.21.3  Setting of temperature alarm monitoring method and alarm 
generation timing 
Examples of temperature alarm monitoring method setting and alarm generation timing are 
shown below. 
  When "Automatic monitoring" is selected; 
[1] Circulating fluid temperature when starting operation: Approximately 20 
o
C 
[2] Circulating fluid set temperature: 15 
o
C 
[3] "AS.21: Temperature alarm monitoring method": Select "Automatic monitoring". 
 ("----" (invalid setting) will be shown for "AS.22: Monitoring start timer".) 
[4] "AS.04: Detection temp. for the circulating fluid discharge temp. rise": Set to "16 
o
C".   
[5] "AS.06: Detection temp. for the circulating fluid discharge temp. drop": Set to "14 
o
C". 
[6] "AS.23: Range over detection timer ": Set to "600 sec". 
 
Fig 5.21-1: Alarm generation timing 
  Alarm generation timing 
Status  (1):  Temperature  alarm  monitoring  starts  by  starting  the  chiller  operation.  As  the 
circulating fluid temperature at this time is 20 
o
C, "AS.06" starts alarm monitoring 
at the same time as the operation start. 
Status (2): The circulating fluid temperature becomes within the set range of "AS.04", and 
starts "AS.04" alarm monitoring. 
Status (3): The circulating fluid temperature exceeds the threshold of "AS.06", but the alarm 
will  not  be  generated  as  it  has  returned  within  the  600  second  range  of  the 
"AS.23: Range over detecting timer". 
Status (4): The circulating fluid temperature exceeds the threshold of "AS.04", but the alarm 
will  not  be  generated  as  it  has  returned  within  the  600  second  range  of  the 
"AS.23: Range over detecting timer". 
Status (5): Alarm "AL03: Circulating fluid discharge temp. rise" will be generated after 600 
seconds  that  is  set  for  the  "AS.23:  Range  over  detection  timer"  after  the 
circulating fluid temperature exceeds the threshold of "AS.04". 
Thermo chiller
Run
Stop
Circulating fluid
set temperature
15
o
C
AS.04 Alarm monitoring
ON
OFF
Alarm
Generation
Nothing
50min
600sec
Circulating fluid
temperature
ON
OFF
250sec
500sec
Elapsed time
AS.04
set temperature 16
o
C
AS.06
 set temperature 14
o
C
1
2
4
3
5
6
AS.06 Alarm monitoring