Chapter  7   Control,  Inspection  and  Cleaning 
HRSH Series  7.1 Quality Control of Circulating Fluid and Facility Water 
 
7-1   
Chapter 7  Control, Inspection and 
Cleaning 
7.1  Quality Control of Circulating Fluid and Facility 
Water 
 
 
 
Table 7-1    Quality criteria for clean water (tap water) 
Electric conductance   
(at 25 
o
C) 
Acid consumption   
(at pH 4.8) 
Should not be 
detected any 
Should not be 
detected any 
Quoted from the standard “JRA-GL-02-1994”, The Japan Refrigeration and Air Conditioning Industry 
Association. 
 
 
Replace the circulating fluid and/or the facility water if any problems 
are found in the regular check. Even if no problems are found, some of 
the water in the tank evaporates and impurity concentration in the 
circulating fluid increases. Replace the circulating fluid on the tank 
once in every 3 months. Refer to the section "7.2 Inspection and 
Cleaning" for regular inspection. 
Use specified fluids only. If other fluids are used, they may damage the 
product, causing fluid leakage, or result in hazards such as electric 
shock or leakage of electricity. 
When using clear water (tap water), ensure that it satisfies the water 
quality criteria shown in the table below.