Chapter  7   Control,  Inspection  and  Cleaning 
HRSH Series  7.4 Operation Stop for an Extended Period of Time 
 
7-7   
7.4  Operation Stop for an Extended Period of Time 
If there is a concern that the product will not be operated for an extended 
period of time or there is a possibility of freezing in the winter time, take the 
measures according to the instructions shown below. 
1.  Turn  OFF  the  earth  leakage  breaker  of  the  user’s  power  supply.  (For 
HRSH--40-turn the breaker handle to the OFF position as well.   
Turn  OFF  the  breaker  inside  the  panel  also  when  the  option  B,  withearth  leakage 
breaker, has been selected.) 
 
2.  Discharge all the circulating fluid completely from the thermo-chiller. 
Refer to ’’7.4.1 Discharge of the circulating fluid’’ for the method of drain the circulating 
fluid from the product. 
 
3.  After discharging the circulating fluid, cover the product with a sheet (to be prepared by 
user) before storing the product.   
 
7.4.1 Discharge of the circulating fluid 
 
 
1.  Turn OFF the breaker of the user’s power supply. 
 
2.  Close the valve at the automatic water fill port. 
 
3.  Open the ball valve at the tank drain port, and discharge the circulating fluid. 
 
4.  Confirm that all the circulating fluid has been discharged completely from the user’s 
equipment  and  piping,  and  then  purge  air  to  the  circulating  fluid  outlet  port  of  the 
product.   
 
5.  Close the ball valve after discharging the circulating fluid. 
  Before discharging the circulating fluid, stop the user’s equipment 
and release the residual pressure.