Chapter  3   Transport  and  Setting  Up 
 
3.3 Installation  HRSH Series 
 
  3-26 
3.3.8 RS-485 communication wiring 
Serial communication RS-485, operation Start/Stop, setting and reading of 
circulating fluid temperature, and reading of alarm condition can be 
performed by remote control. 
Refer to Operation Manual Communication Function for more details. 
  Wiring of interface communication cable 
 
 
 
 
 
 
 
Connecting to PC 
RS-485 cannot be directly connected to a normal PC. Use an 
RS-232C/RS485 converter which is available on the market. 
Be sure to follow the wiring procedure shown below for connecting multiple 
thermo-chillers. 
 
 
Configuration of connection 
One thermo-chiller for one host computer, or multiple thermo-chillers for one 
host computer. 
(31 thermo-chillers can be connected at maximum.) 
 
 
Fig. 3-14 Connection of RS-485 
[Tips]
 
 
Both  ends  of  the  communication  connection  (the  end  nodes)  need  to  be 
connected to the host computer. 
With or without the terminating resistor (120Ω) of this product can be set by 
the operation display panel. Refer to “5.22 Communication Function”. 
1
SD+
5
SG
9
SD-
SD+
SD- SG
Terminal
resistance
Master This product
(first slave)
1
SD+
5
SG
9
SD-
This product
(second slave)
1
SD+
5
SG
9
SD-
This product
(31
st
 slaves)
Terminal
resistance120Ω
  Be sure to turn OFF the breaker of the facility power supply (the 
user's machine power supply) before wiring.