HRX-OM-Q026 
Chapter  5   Display  and  Setting  of  Various  Functions 
 
5.21 Alarm Customizing Function  HRSH Series 
 
  5-48 
5.21 Alarm Customizing Function 
5.21.1  Alarm customizing function 
Operation and trigger level when an alarm signal is output can be 
customized. Perform settings depending on the application of the user. 
Refer to “Table 5.21-1 Default alarm settings and customizing (1/4)” and 
“Table 5.21-4 Default alarm settings and customizing (4/4)” for the items 
that can be customized for each alarm. 
1. Alarm operations   
A.STP: Operation of compressor, fan, and pump stop 
*1 
A.RUN: Operation of compressor, fan, and pump continues.   
P.RUN: Compressor and fan stop operation, and pump 
continues operation.
*1 and 2 
OFF: This alarm will not be generated. 
- Symbol or each    operation 
○  : Initial setting 
●  : Possible to select 
-  : Impossible to select 
*1: Fan when the anti-snow coverage function is ON operates as explained in "5.19 Anti-Snow Coverage 
Function". 
*2: The alarm operations of all the object alarms of the P.RUN cannot be customized individually but collectively. 
2. Alarm thresholds and others 
This shows the settable range. Settings can be changed from default within this range. 
Settings shown with "-" cannot be changed. 
 
Table 5.21-1 Default alarm settings and customizing (1/4) 
1. Operation during alarm 
generation 
2. Threshold for alarm generation and 
other settings
1
 
High circulating 
fluid discharge 
temp. 
Circulating fluid 
discharge temp. 
rise 
40.0 
o
C 
(104.0 
o
F) 
(----)
2
 
5.0 to 55.0 
o
C 
(41.0 to 131.0 
o
F) 
Range over detection timer 
1: Values in  ゚ F are displayed when SE12 is set to F. 
2: Default value when AS03 is set OFF. 
3: Default value when AS21 is set to either 2 or 3.