HRX-OM-Q026
Chapter 5 Display and Setting of Various Functions
HRSH Series 5.21 Alarm Customizing Function
5-49
Table 5.21-2 Default alarm settings and customizing (2/4)
1. Operation during alarm
generation
2. Threshold for alarm generation and
other settings
4
Circulating fluid
discharge temp.
drop
1.0
o
C
(33.8
o
F)
(----)
5
1.0 to 34.0
o
C
(33.8 to 93.2
o
F)
Range over detection timer
High circulating
fluid return temp.
Circulating fluid
discharge pressure
rise
Set pressure (HRSH250/300-A)
1.00 MPa
(145 PSI)
(----)
7
0.05 to 1.00 MPa
(7 to 145 PSI)
Set pressure (Other models)
0.70 MPa
(102 PSI)
(----)
7
0.03 to 0.70 MPa
(4 to 102 PSI)
Circulating fluid
discharge pressure
drop
Set pressure (HRSH250/300-A)
0.05 MPa
(7 PSI)
(----)
8
0.05 to 1.00 MPa
(7 to 145 PSI)
Set pressure (Other models)
0.03 MPa
(4 PSI)
(----)
8
0.03 to 0.70 MPa
(4 to 102 PSI)
High compressor
intake temp.
Low compressor
intake temp.
High compressor
discharge pressure
Refrigerant circuit
pressure (high
pressure side) drop
Refrigerant circuit
pressure (low
pressure side) rise
4: Values are shown in
o
F when the unit is set to F for SE12, and in PSI when the unit is set to PSI for SE13.
5: Default value when AS05 is set OFF.
6: Default value when AS21 is set to either 2 or 3.
7: Default value when AS07 is set OFF.
8: Default value when AS09 is set OFF.