50
Wiring
Cable seal
ring Tail cover
Figure 7-11 Inserting the stripped wire
Step 3: With care, strip the cable jacket about 15±1 mm from the end.
15 ± 1 mm
Conductor
Cable jacket
Wire stripper
Figure 7-12 Striping cable jacket
NOTICE!
DO NOT damage the conductor while sliding the jacket off the power cable end.
The wire size of the power cable delivered with the accessories kit is 25 mm (3 AWG).
Step 4: Fit the connector body over the conductor strands, and squeeze the crimper to
crimp the terminal. The conductor strands exposed shall not be over 1 mm.
Plastic
housing
The exposed conductor < 1 mm
7±0.2 mm
Cross section
of joint part
Hydraulic wire crimper
Figure 7-13 Fitting connector body and crimping terminal

Related product manuals