SET PAGE - MENUS
Page 29 of 67
Overload Stall Time Factor).
Config. Input B
External Fault 1
Enables Configuration of Discrete Input B as:
• Contactor A N.O. (for MPS3000-C, for sensing contactor A status).
• All Other settings as in Config. Input A
Config. Input C
External Fault 2
Enables Configuration of Discrete Input C as:
Contactor B N.C. (for MPS3000-C, for sensing contactor B status).
• All Other settings as in Config. Input A
Config. Input D
Remote Reset
Enables Configuration of Discrete Input D as:
Contactor B N.O. (for MPS3000-C, for sensing contactor B status).
All Other settings as in Config. Input A
Protection Only
Yes
Determines MPS operation mode:
Protection & Control (No)
Protection Only (Yes)
Range: Yes, No
Param. Settings
Locked Out
Can be used instead of external “Authorized Key” inputs. When set as “Not
Locked” external key options function normally. When set as Not Locked, external
key inputs are ignored and MPS is in Authorized condition (same as if external
key is connected).
Voltage Settings
Voltage
*** Settings ***
Display Description
U/V Level
80% of Vn
Under Voltage level, (in % of nominal voltage). Fault occurs when voltage is below set
value for more than U/V delay. Range: 50 - 95 % of Vn. Increments of : 1 %
U/V Delay
5.0 Sec.
Under Voltage time delay.
Range: 0.2 - 10 Sec. Increments of : 0.1 Sec.
UV Active at Stop
Disable.
Determines if Under Voltage protection is active at stop. If disabled, u/v is active only if
not at stop.
Range: Disable, Enable
U/V Strt Prevent
OFF
Prevents starting if mains voltage is lower than set by U/V Start Prevent. For MPS3000-
C only.
Range: OFF, 51-95 % of Vn. Increments of : 1%