SET PAGE - MENUS
Page 40 of 67
Communication Settings
Communication
*** Settings ***
Display Description
Baud Rate
19200
Serial Link communication speed in bps. Disconnect and then reconnect
auxiliary supply after any change of baud rate.
Range: 1200, 2400, 4800, 9600, 19200 bps.
Address Number
248
MPS Address on Serial Link. RS485 Allows a maximum of 32 MPS3000s on
a twisted pair.
Range: 1 - 247, 248 = OFF. Increments of: 1
S. Link Save Lock
Locked
When set to Locked, prevents setting through serial link communication.
When set to Not Locked, setting through serial link is enabled.
Range: Locked, Not Locked.
Note: It is only possible to write and read through MODBUS communication (only !, parameters
cannot be displayed on screen and cannot be changed from keyboard) 20 additional setting
parameters. These parameters are numbers of MODBUS actual parameters. By writing to these
parameters, user can define a group of up to 20 parameters that can be scanned as one group. See
the MPS 3000-10 COMMUNICATION Manual for further reference.